To summarize, fireproof coating should not be used as a fire protection measure when steel plate ducts are used for smoke prevention and exhaust ducts. The landmark requirement of external fireproof coating for metal ducts cannot be adopted:
(1) Interpretation of some technical issues in Yunnan Province regarding the Technical Standard for Building Smoke Prevention and Exhaust System (2019.05.17) Article 16: Spraying (coating) fireproof coating - can be used for steel structure warehouse, but should not be used for civil buildings and factories, the reasons are mainly:
First, the fireproof coating volatilizes toxic and harmful gases at high temperature;
Second, the fireproof coating expands and deforms under high temperature, which may hinder the normal action of the actuators such as dampers.
(2) In Suzhou Wujiang District Housing and Urban-Rural Development Bureau document [Wuzhujian Consumption (2020) No. 18], 'Some Guidelines on Common Problems in Fire Protection Design of Construction Projects', (14) Fireproof coating shall not be applied as a measure to meet the fire resistance limit of the air supply and smoke exhaust ducts.
(3) Xuzhou City Refrigeration Society Xuzhou City Civil Engineering Society HVAC Specialized Committee 'Building Smoke Prevention and Exhaust System Technical Standard' GB51251-2017 Xuzhou Regional Technical Seminar for Examiners (Version 2.0.2) Article 7: Spraying (coating) fireproofing coatings - can be used in steel structure warehouses, but should not be used in civil buildings and factories, the reason is mainly:
First,Fireproof coating volatilizes toxic and harmful gases at high temperature;
Second, Fireproof coating expands and deforms under high temperature, which may hinder the normal operation of the actuators such as dampers.